Description
Shop with Confidence
Brand new Australian StockNo Factory Seconds
Full Australian Manufacturer's Warranty
Secure Online Payments
Description
9 kW Cooling10 kW Heating
Single Fan Heat Pump VRF O/U
Specifications
SERIES | PUMY-SP (Single Fan) | |||||||
Model | PUMY-SP80VKMD-A | |||||||
Power Source | VKMD: YKMD: | 1-phase 220-230-240 3-phase 380-400-415 | V, 50 Hz; 1-phase 220 V, 50 Hz; 3-phase 380 | V, 60 Hz V, 60 Hz | ||||
Cooling Capacity | kW | 9 | .0 | |||||
(Nominal)*1 Temperature Range of Cooling | Power Input | kW | 2. | 11 | ||||
Current Input | A | 9.79 9.36 8.97 | 3.37 3.21 3.09 | |||||
EER | kW | 4. | 27 | |||||
AEER Indoor | kW W.B | 3. | 35 | |||||
15.0 ~ | 24.0 C | |||||||
Outdoor | D.B | -5.0 ~ 52.0 | C *3 *4 *5 | |||||
Heating Capacity | kW | 1 | 0.0 | |||||
(Nominal)*2 Temperature Range of Heating | Power Input | kW | 2. | 27 | ||||
Current Input | A | 10.53 -10.07 9.65 | 3.63 3.45 3.32 | |||||
COP | kW | 4. | 41 | |||||
ACOP Indoor | kW W.B | 3. | 62 | |||||
15 ~ | 27 C | |||||||
Outdoor | D.B | -20 ~ | 15 C | |||||
Indoor Unit Connectable Sound Pressure Level (measured in anechoi | Total Capacity | 50% to 130% of Ou | tdoor Unit Capacity | |||||
Model/Quantity c room) | dB | P10- | P100/9 | |||||
51/ | 54 | |||||||
Refrigerant Piping Diameter | Liquid Pipe | mm (in.) | 9.52 (3 | /8) Flare | ||||
Gas Pipe | mm (in.) | 15.88 ( | /8) Flare | |||||
Fan | Type x Quantity | Propelle | r Fan _ 1 | |||||
Airflow Rate | m3/min | 7 | 5 | |||||
L/s | 12 | 50 | ||||||
cfm | 26 | 49 | ||||||
Control, Driving Mechanism | DC C | ontrol | ||||||
Motor Output | kW | 0.20 | _ 1 | |||||
Compressor | Type x Quantity | Twin Rotary Herme | tic Compressor _ 1 | |||||
Manufacturer | Mitsubishi Elec | tric Corporation | ||||||
Starting Method | Inv | erter | ||||||
Motor Output | kW | 2 | .1 | |||||
Lubricant | FV50S ( | 1.4 litre) | ||||||
External Finish External Dimension (H x W x D) | mm | Galvanised Steel Shee | t Munsell No. 3Y 7.8/1. | 1 | ||||
981 _ 1,050 | _ 330 (+25) | |||||||
Protection Devices | High Pressure Protection | High Pres | sure Switch | |||||
Inverter Circuit (COMP./FAN) | Overcurre | nt Detection, Overheat | detection (Heat Sink | Thermistor) | ||||
Compressor | Compressor Thermisto | r, Overcurrent Detectio | n | |||||
Fan Motor | Overheating, V | oltage Protection | ||||||
Refrigerant Net Weight | Type x Original Charge | R410A | _ 3.5 kg | |||||
Control | kg | Electronic Ex | pansion Valve | |||||
93 *5 *6 | 94 *7 | 93 *6 | 94 *7 | |||||
Heat Exchanger | Cross Fin an | d Copper Tube | ||||||
HIC Circuit (HIC: Heat Inter-Changer) | HIC | Circuit | ||||||
Defrosting Method Drawing | External | Reversed Ref | rigerant Circuit | |||||
RK0 | 1J091 | |||||||
Wiring | BH79N194 | BH79N195 | BH79N194 | BH79N195 | BH79N194 | BH79N195 | ||
Standard Attachment | Document | Installation Manual | ||||||
Accessory | Grounded Lead Wire | |||||||
Optional Parts | Joint: CMY-Y62-G-E Header: CMY-Y64/68-G-E |
Package Description
Mini VRF Single Fan PUMY-SPThe PUMY-SP series allows up to 10 indoor units to be connected to a single outdoor unit, using the standard City Multi branch pipework system or via branch boxes to connect M Series and Mr Slim indoor units. This makes it an economic and efficient answer for multi-room applications, whilst also offering space saving benefits. Each size is available in both single and three phase options.
Compact and out of sight
The Mini VRF Single Fan PUMY-SP compact design has a reduced footprint with a 27% reduction in height and 25% reduction in weight, allowing it to be installed in more confined spaces compared to the dual fan model.
The reduced height (less than one metre) makes this unit suitable for installation on balconies. The weight reduction makes the unit easier facilitates easier installation and transportation.
Flexible connection
The outdoor unit allows piping from any four directions; front, back, bottom, or right. This enables easier horizontal connection for collective layout. The outdoor unit with an expanded piping layout improves piping workability.
Super quiet mode*
Noise level can be reduced up to 10dB(A). This allows you to operate the unit even in the night in a residential zone.
* Capacity reduction differs by mode setting. PAC-SC36NA-E is required to activate Super Quiet mode by external input.
External static pressure of 30Pa
The installation location is flexible, thanks to the 30Pa static pressure. An external static pressure of 30Pa allows outdoor unit to be installed on balconies in high-rise building or spaces near louvers.
Energy efficiency
Despite its compact size and low weight, the new Mini VRF Single Fan PUMY-SP features high efficiency.
Connectivity
Mini VRF Single Fan PUMY-SP single-fan units can be connected to the indoor units of Residential M Series and Commercial Mr Slim and CITY MULTI series using PAC-MK-BC branch boxes.
It's possible to mix and match Residential and Commercial indoor units, providing great flexibility for solving system design challenges.
Buyers Guide
Product Availability
We do not list stock levels on our website due to the wide variety of products we carry. Some items are directly sourced from suppliers, while others are stored in our partner local warehouses across Sydney, Brisbane, and Melbourne.
Once you has been confirmed, it undergoes a thorough processing stage to ensure all details are accurate. During this time, we check stock availability within 24 to 72 business hours.
If any supply issues arise, a member of our customer service team will promptly reach out to you via phone, email, or text to confirm your order and provide an update on the stock status.
FAQ, Warranty & Returns
All systems sold by Wholesale Aircon have a 5 year manufacturers warranty. For more details refer to each Manufacturers warranty guidelines.
Important Information to Maintain Your Warranty!
- Keep a copy of your invoice
- Ensure your air conditioning installer is qualified and holds a current refrigeration handling license.
- Ensure operation is as per manufacturer’s instructions.
- Ensure the air inlet and outlet of the outdoor unit is kept clear of obstructions.
- Replace exhausted batteries in remote control.
- If your system fails, contact the manufacturer without delay.
We are unable to deliver to a PO Box as we need ID and a copy of the online receipt when delivery is made.
Wholesale Aircon can help guide you if a warranty issue arises. Firstly the client needs to contact the manufacturer. The number for each manufacturer will be on the warranty form which came with the system purchased. When placing a warranty claim you will need to provide proof of purchase (your tax invoice).
We are always looking to expand our product range and are constantly releasing the latest products and models.
The cooling and heating capacity of an air conditioner is measured in kilowatts (kW).
Airconditioner Sizing Guide
2.5 kW RANGE
SUITABLE FOR ROOMS APPROX 10 – 25 SQ METERS
- Bedrooms
- Studys
- Small lounges
- Small kitchens
- Small offices
3.5kW RANGE
SUITABLE FOR ROOMS APPROX 25 – 35 SQ METERS
- Bedrooms
- Bedrooms with ensuites
- Studys
- Small lounges
- Mid-sized kitchens
- Small rooms with high ceilings
- Offices
5 – 6kW RANGE
SUITABLE FOR ROOMS APPROX 35 – 60 SQ METERS
- Large bedrooms
- Bedrooms with ensuites
- Studys
- Mid-size lounges
- Large kitchens
- Mid-sized rooms with high ceilings
- Offices
7 – 8kW RANGE
SUITABLE FOR ROOMS APPROX 60 – 80 SQ METERS
- Large lounges
- Large open plan areas
- Small shops
- Offices
For more complex installations a heat load calculation should be performed. A heat load calculation comprises of many factors such as size of area, size of windows, roof type, building material, whether there is insulation, external shading or internal shading etc. Incorrect sizing will mean inadequate cooling/heating.
If you are unsure on sizing please email us, or go to Request a Quote or call 0473 575 383
FAQ, Warranty & Returns
If we still haven't answered your question, you can contact us below and we will get back to you as soon as possible.